Motor Protection - Quick Start Guide Installation
DV Series dV/dt and SW Series Sinewave Output Filters
Mounting the Output Filter
- If wall-mounted, loosen attached mounting brackets, rotate such that mounting hole extends above the chassis, and re-tighten.
- If floor-mounted, fasten legs using concrete anchors or similar.
- Intake and exhaust openings must not be obstructed. If mounted in an enclosed space temperature must remain below 40 C (104 F). Notes: 18" (450mm) clearance below and 12" (150mm) around required for ventilation.
Connect Wiring
Installation should be performed by a licensed electrician and comply with all applicable electrical codes.
- Ensure power is disconnected from the variable frequency drive (VFD).
- Remove front panel from output filter and route cables through supplied conduit openings in bottom of enclosure.
Note: Continuous metal conduit should be used for all power cables to reduce radiated electromagnetic interference (EMI). -
Install ground wires from both motor and VFD to the ground lugs provided in the filter enclosure.
- Connect the motor power wires to the output of the filter (U2, V2, W2).

- Connect the output wires from the VFD to the input terminals of the output filter (U1, V1, W1).

WARNING!
in damage and will void warranty.

Powering the Filter
- Re-install the front panel of the output filter.
- Ensure all VFD settings are compatible with the output filter and motor being used.
- Verify the Startup Checklist (see below).
- Reconnect power to and run the VFD.
Startup Checklist
- Filter is securely attached to the proper mounting surface.
- Filter ground terminals are properly bonded to earth ground.
- Filter input terminals are connected to the output of a VFD and the VFD is configured properly:
- VFD output frequency is less than 90 Hz.
- VFD PWM switching frequency is between 2 kHz and 8 kHz.
- VFD operation mode is Volts per Hertz without DC braking.
- Note: VFD motor auto-tuning procedures will be greatly affected and likely will result in inaccurate results. Consult with VFD supplier if auto-tuning is desired with filter installed.
- VFD, motor, and filter are ALL of an appropriate rating.
- Motor is connected to the filter output terminals.
- Motor is secured and properly mounted.