Phase Connect - Quick Start Guide Configuration
QUICKSTART PC4R, Revision 001
The device name, location, labels, 4-20 mA sensor range, and 4-20 mA sensor units may be configured from the Config tab of the Phase Connect web portal.
Once configured, the status of the Phase Connect and attached devices may be monitored or controlled from the Dashboard tab.
Common Wiring Configurations
Detect VFD Faults
Phase Technologies VFD Settings:
PROGRAM RELAY 1 = SYSTEM FAULT
Repeat 4-20 mA Input Signal
The 4-20 mA signal can be monitored via the web portal and will also be sent (replicated) to the VFD for control.
Phase Technologies VFD Settings:
SYSTEM CONFIG = Speed Control Proportional to 4-20 mA Signal
Phase Connect Settings:
4-20 mA Output = "Match Input" Enabled
Monitor VFD Run Status
Phase Technologies VFD Settings:
PROGRAM RELAY 2 = MIN FREQUENCY
Control VFD Run Status
Will allow the use of Relay 1 control within the web portal to give the VFD a RUN or STOP command.
Phase Technologies VFD Settings:
SYSTEM CONFIG = RUN/STOP using AUX1 and AUX2
AUX1 SELECT = Closed=RUN, Open=STOP