Phase Connect -
Quick Start Guide
Configuration

QUICKSTART PC4R, Revision 001

The device name, location, labels, 4-20 mA sensor range, and 4-20 mA sensor units may be configured from the Config tab of the Phase Connect web portal.

Once configured, the status of the Phase Connect and attached devices may be monitored or controlled from the Dashboard tab.


Common Wiring Configurations

Detect VFD Faults

Phase Technologies VFD Settings:
PROGRAM RELAY 1 = SYSTEM FAULT

Repeat 4-20 mA Input Signal

The 4-20 mA signal can be monitored via the web portal and will also be sent (replicated) to the VFD for control.

Phase Technologies VFD Settings:
SYSTEM CONFIG = Speed Control Proportional to 4-20 mA Signal
Phase Connect Settings:
4-20 mA Output = "Match Input" Enabled


Monitor VFD Run Status

Phase Technologies VFD Settings:
PROGRAM RELAY 2 = MIN FREQUENCY

Control VFD Run Status

Will allow the use of Relay 1 control within the web portal to give the VFD a RUN or STOP command.

Phase Technologies VFD Settings:
SYSTEM CONFIG = RUN/STOP using AUX1 and AUX2
AUX1 SELECT = Closed=RUN, Open=STOP




Documents

Phase Connect Installation

Looking for the Phase Connect Installation Guide? See the Phase Connect Installation Quick Start Guide.

Read more

Download
Phase Connect Manual
phasetechnologies.com/support/pc